Corrosion Inhibitor
EVERYONE ELSE’S FIREPROOFING CONTRIBUTES TO CORROSION. WE INHIBIT IT.
TEST REPORT
SALT SPRAY (FOG) TEST ASTM B-117
Geopolymer Solutions, LLC
11200 Cox Road
Conroe, Texas 77385
10-01-18
Report No.: C19-144
OBSERVATIONS
After completion of 5000 hours of salt spray exposure test, all four insulated steel panels were evaluated for presence of spot rusting, and corrosion attack to the metal substrate protected by insulation. A small area of insulation from each sample was removed to inspect the condition of the metal substrate. Visual examination revealed that the metal substrate under the insulation was virtually free from any spot rusting or corrosion damage due to salt spray exposure testing. Furthermore, it appears that the protection of the metal substrate under the insulation is independent of insulation thickness.
REMARKS
The following samples were submitted:
- Insulated panel Marked #1 having 3/8” of insulation thickness (Scribed an X thru insulation)
- Insulated panel Marked # 2 having 5/8” of insulation thickness
- Insulated panel Marked #3 having 3/4” of insulation thickness (Scribed an X thru insulation)
- Insulated panel Marked #4 having 1-1/2” of insulation thickness
Test Samples | Four steel panels covered with insulation material ( Cold Fusion Concrete FP250) on one surface. |
Size of Sample | 8”x 3”x 1/4” |
Test Duration | 10,000 Hours |
Test Started | 2-11-2019 |
Test Completed | 05-06-2019 |
Humidifying Tower Temperature | 112°F |
Air Pressure | 15 psig |
Solution Concentration | 5% NaCl |
Solution pH | 7 |
Volume of Salt Solution Collected | 1.6 ml/hr. |